OVERVIEW
Attractively styled, our new SMW360 room occupancy detector is built to the highest specification and incorporates the latest microwave technology.
The unit uses very low powered microwave Doppler detection to sense whether the room is occupied and is simple to install requiring only line and neutral and a line feed to the load using screw-less terminals. Time on, ambient light level (Lux) and range detection are adjustable using screws housed under the bayonet fit cover. The unit uses very low powered microwave Doppler detection to sense whether the room is occupied and is simple to install requiring only line and neutral and a line feed to the load using screw-less terminals.
Time on, ambient light level (Lux) and range detection are adjustable using screws housed under the bayonet fit cover.
SPECIFICATIONS
| Supply | 220–240VAC 50Hz |
| Power consumption | 0.5W Approximately |
| Siting | For internal use only,wall or ceiling mounting, up to 4m in height |
| Detection | Microwave 5.8GHz CW, ISM band, transmission power <10mW |
| Coverage | Horizontal 360°, vertical 160°, adjustable up to 16m |
| Time setting | Adjustable 8 sec to 12 min |
| Ambient light control | Adjustable 2–2000LUX (night to daylight) |
| Rating | IP44 |
MAXIMUM LOADS
| Resistive | 16A 240VAC |
| Incandescent | 1000W |
| Halogen lamps | 500W |
| LV halogen lamps | 200W |
| Fluorescent lamps | 150W (uncompensated) |
| Examples | 6 x 18W, 4 x 36W, 2 x 59W |
| LED lamp | 150W |
| Energy saving lamps | 100W (including CFL & PL) |
| Discharge lamps | A suitable contactor is recommended |
DETECTION PATTERNS
Click link to view
DOWNLOADS
Click link to download